Power Factor Correction Calculator

Enter the load in kW, the present power factor and the power factor you want. The calculator gives the capacitor bank size and what it saves in kVA and current.

Calculator

Above 0 and below 1

Above the existing value, up to 1

Reset

Result

Capacitor needed
55.323 kVAr
Apparent power before
133.33 kVA
Apparent power after
105.26 kVA
kVA saved
28.07 kVA (21.053 %)
Current before
185.49 A
Current after
146.44 A
Capacitance per phase (delta)
340.83 µF

How it works

Motors, transformers and other inductive loads draw reactive power as well as real power, so the supply must carry more current than the kW alone would need. A low power factor means bigger cables, more loss and, in many tariffs, a penalty.

Capacitors supply reactive power locally. The bank size is the difference between the reactive power before and after: Qc = kW × (tan φ1 − tan φ2). Raising the power factor lowers the kVA and the line current for the same kW.

The capacitance is given for a delta connected three phase bank, or for a single capacitor on a single phase supply. Large motor loads, harmonics and switching need a proper design, for example detuned reactors and an automatic controller.

Formulas used

  • Qc (kVAr) = kW × (tan φ1 − tan φ2), with φ = arccos(power factor)
  • kVA = kW ÷ power factor
  • Current = kVA × 1000 ÷ (√3 × V) three phase, kVA × 1000 ÷ V single phase
  • Capacitance per phase (delta) C = Qc × 1000 ÷ (3 × 2π f × V²)

Worked example

A 100 kW load at power factor 0.75 raised to 0.95 needs 100 × (0.882 − 0.329) = 55.3 kVAr. The kVA falls from 133.3 to 105.3 and the current on 415 V from 185.5 A to 146.4 A.

The calculator opens with these example values, so you can compare its answer with the text above.

Frequently asked questions

How do I calculate the capacitor size to improve power factor?

Multiply the kW by the difference of tan φ before and after, where φ is the angle whose cosine is the power factor.

What is a good target power factor?

Many utilities ask for 0.95 or better. Going to 1.0 is rarely worth the cost and can over-correct at light load.

Why does a low power factor cost money?

It raises the current for the same useful power, which needs larger equipment and increases losses. Many tariffs also charge for kVA or penalise a low power factor.

Can I use any capacitor?

No. Use capacitors rated for the voltage and duty, with protection, and have the bank designed for your load and harmonics.